Cassette

OLMO Classic Series
Cassette:

  • Wide angle airflow ideal for offices
  • Built-in drain pump with a lift height up to 500 mm
  • Three fan speeds
  • Fan with low noise level created by aerodynamic configuration "three-dimensional screw"
  • The ability to connect individual wired remote control. The control commands from Central control.
  • Organization of control using the Central console
Model   OSH-T12HR
Productivity Cool kW 3,20
Heat kW 4,00
Power supply     220-240V/50Hz
Nominal power consumption Cool kW 1,08
Heat kW 1,23
Energy efficiency E.E.R. (Cool)   2,96
C.O.P. (Heat)   3,25
The Air performance indoor unit m3/h 400/600/680
outdoor unit m3/h 2100
Noise level indoor unit dB(A) 34/36/40
outdoor unit dB(A) 41
Dimensions (width/height/depth) indoor unit mm 570x260x570
panel. indoor unit mm 647x50x647
outdoor unit mm 780x547x250
Weight indoor unit kg 16
outdoor unit kg 34
Operating temperature range Cool °C +18/+43
Heat °C -7/+24
The diameter of the liquid line mm/inch 6,35 / 1/4"
The diameter of the gas pipeline mm/inch 12,70 / 1/2"
The diameter of the drain pipe mm 25
The maximum elevation on the line m 8
The maximum line length m 15
The distance between the mounting bolts of the outdoor unit mm 624
Factory refrigerant charge (on the number of linear meters)   5
Model   OSH-T18HR
Productivity Cool kW 5,30
Heat kW 6,00
Power supply     220-240V/50Hz
Nominal power consumption Cool kW 1,83
Heat kW 1,88
Energy efficiency E.E.R. (Cool)   2,90
C.O.P. (Heat)   3,19
The Air performance indoor unit m3/h 500/760/860
outdoor unit m3/h 2439
Noise level indoor unit dB(A) 36/40/42
outdoor unit dB(A) 50
Dimensions (width/height/depth) indoor unit mm 570x260x570
panel. indoor unit mm 647x50x647
outdoor unit mm 762x593x282
Weight indoor unit kg 19
outdoor unit kg 39
Operating temperature range Cool °C +18/+43
Heat °C -7/+24
The diameter of the liquid line mm/inch 6,35 / 1/4"
The diameter of the gas pipeline mm/inch 12,70 / 1/2"
The diameter of the drain pipe mm 25
The maximum elevation on the line m 15
The maximum line length m 25
The distance between the mounting bolts of the outdoor unit mm 624
Factory refrigerant charge (on the number of linear meters)   5
Model   OSH-T24HR
Productivity Cool kW 7,10
Heat kW 7,60
Power supply     220-240V/50Hz
Nominal power consumption Cool kW 2,47
Heat kW 2,43
Energy efficiency E.E.R. (Cool)   2,88
C.O.P. (Heat)   3,13
The Air performance indoor unit m3/h 871/1114/1327
outdoor unit m3/h 3200
Noise level indoor unit dB(A) 37/40/42
outdoor unit dB(A) 52
Dimensions (width/height/depth) indoor unit mm 840x230x840
panel. indoor unit mm 950x55x950
outdoor unit mm 845x695x324
Weight indoor unit kg 24
outdoor unit kg 53
Operating temperature range Cool °C +18/+43
Heat °C -7/+24
The diameter of the liquid line mm/inch 9,53 / 3/8"
The diameter of the gas pipeline mm/inch 15,88 / 5/8"
The diameter of the drain pipe mm 32
The maximum elevation on the line m 15
The maximum line length m 25
The distance between the mounting bolts of the outdoor unit mm 624
Factory refrigerant charge (on the number of linear meters)   5
Model   OSH-T36HR
Productivity Cool kW 10,50
Heat kW 12,00
Power supply     380-415V/50Hz
Nominal power consumption Cool kW 3,78
Heat kW 4,25
Energy efficiency E.E.R. (Cool)   2,78
C.O.P. (Heat)   2,82
The Air performance indoor unit m3/h 1187/1354/1545
outdoor unit m3/h 5000
Noise level indoor unit dB(A) 39/41/44
outdoor unit dB(A) 54
Dimensions (width/height/depth) indoor unit mm 840x300x840
panel. indoor unit mm 950x55x950
outdoor unit mm 990x966x354
Weight indoor unit kg 30
outdoor unit kg 92
Operating temperature range Cool °C +18/+43
Heat °C -7/+24
The diameter of the liquid line mm/inch 12,70 / 1/2"
The diameter of the gas pipeline mm/inch 19,05 / 3/4"
The diameter of the drain pipe mm 32
The maximum elevation on the line m 20
The maximum line length m 30
The distance between the mounting bolts of the outdoor unit mm 624
Factory refrigerant charge (on the number of linear meters)   5
Model   OSH-T48HR
Productivity Cool kW 14,00
Heat kW 15,00
Power supply     380-415V/50Hz
Nominal power consumption Cool kW 4,88
Heat kW 5,29
Energy efficiency E.E.R. (Cool)   2,87
C.O.P. (Heat)   2,84
The Air performance indoor unit m3/h 1187/1354/1545
outdoor unit m3/h 6800
Noise level indoor unit dB(A) 40/42/44
outdoor unit dB(A) 56
Dimensions (width/height/depth) indoor unit mm 840x300x840
panel. indoor unit mm 950x55x950
outdoor unit mm 900x1167x340
Weight indoor unit kg 30
outdoor unit kg 110
Operating temperature range Cool °C +18/+43
Heat °C -7/+24
The diameter of the liquid line mm/inch 12,70 / 1/2"
The diameter of the gas pipeline mm/inch 19,05 / 3/4"
The diameter of the drain pipe mm 32
The maximum elevation on the line m 25
The maximum line length m 50
The distance between the mounting bolts of the outdoor unit mm 590
Factory refrigerant charge (on the number of linear meters)   5
Model   OSH-T60HR
Productivity Cool kW 16,00
Heat kW 19,00
Power supply     380-415V/50Hz
Nominal power consumption Cool kW 5,90
Heat kW 6,86
Energy efficiency E.E.R. (Cool)   2,71
C.O.P. (Heat)   2,77
The Air performance indoor unit m3/h 1280/1480/1800
outdoor unit m3/h 6850
Noise level indoor unit dB(A) 42/44/46
outdoor unit dB(A) 58
Dimensions (width/height/depth) indoor unit mm 840x300x840
panel. indoor unit mm 950x55x950
outdoor unit mm 900x1167x340
Weight indoor unit kg 30
outdoor unit kg 106
Operating temperature range Cool °C +18/+43
Heat °C -7/+24
The diameter of the liquid line mm/inch 12,70 / 1/2"
The diameter of the gas pipeline mm/inch 19,05 / 3/4"
The diameter of the drain pipe mm 32
The maximum elevation on the line m 25
The maximum line length m 50
The distance between the mounting bolts of the outdoor unit mm 590
Factory refrigerant charge (on the number of linear meters)   5